Compare Equipment Go Back

CG260-16 Gas Generator Set
EMCP 4.4 Master Control Panel
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Continuous Rating 4500 / 4050 ekW @1.0pf - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - -
Maximum Electrical Efficiency 44.60 / 44.3% - -
Maximum Standby Rating 4500 ekW - -
Frequency 50 / 60 Hz - -
RPM 1000 / 900 rpm - -

Generator Set Dimensions

Length 371 in - -
Width 110 in - -
Height 133 in - -
Dry Weight - Genset 117505 lb - -

Engine Specifications

Engine Model CG260-16 - -
Displacement 16586 in³ - -
Stroke 12.6 in - -
Bore 10.2 in - -
Aspiration TA - -

Technical Summary

Configuration - Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source. Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - Emergency standby, island, utility paralleling Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV (208V - 38 kV) LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - IBC, CBC, UBC & OSHPD Certified UL / cUL 508A
Control Panel Enclosure - NEMA 1 wall-mounted construction NEMA 12
Operating Temperature - 0°C to 50°C 0°C to 55°C
Storage Temperature - -20°C to +60°C -20°C to 60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 -
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 -
Add a Similar Product:
  • Cat Switchgear Add
  • Cat Customizable Switchgear and Controls Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add