Compare Equipment Go Back

CG260-16 Gas Generator Set
Cat Customizable Switchgear and Controls
Engine Paralleling and Integration Control (EPIC)

Generator Set Specifications

Continuous Rating 4300 / 4000 ekW @1.0pf - -
Fuel Type Natural Gas, Biogas, Coal Gas, Associated Gas, Synthesis Gas, Hydrogen Blend (to 25%) - -
Maximum Electrical Efficiency 44.1 / 43.8% - -
Maximum Standby Rating 4500 ekW - -
Frequency 50 / 60 Hz - -
RPM 1000 / 900 rpm - -

Engine Specifications

Engine Model CG260-16 - -
Displacement 16586 in³ - -
Aspiration TA - -
Bore 10.2 in - -
Stroke 12.6 in - -

Generator Set Dimensions

Length 371 in - -
Width 110 in - -
Height 133 in - -
Dry Weight - Genset 117505 lb - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V-27kV)

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - Per customer specification UL / cUL 508A
Control Panel Enclosure - Per customer specification NEMA 12
Operating Temperature - Per customer specification 0°C to 55°C
Storage Temperature - Per customer specification -20°C to 60°C
Low Voltage Standards - Per customer specification -
Medium Voltage Standards - Per customer specification -
Add a Similar Product:
  • Cat XLM Switchgear Add
  • Cat Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • XQ425 Add