G3520H Gas Generator
Cat Customizable Switchgear and Controls
EMCP 4.4 Master Control Panel

Generator Set Specifications

Continuous Rating 2519 / 2500 ekW @ 1.0pf - -
Fuel Type Natural Gas, Hydrogen Blend (up to 25%) - -
Maximum Electrical Efficiency 45.30% - -
Frequency 50/60 Hz - -
RPM 1500 - -

Engine Specifications

Engine Model G3520H - -
Displacement 5956 in³ - -
Aspiration TA - -
Bore 6.7 in - -
Stroke 8.5 in - -
Compression Ratio 12.1 - -

Generator Set Dimensions

Length 302 in - -
Width 86 in - -
Height 97 in - -
Dry Weight - Genset 54675 lb - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency standby, island, utility paralleling
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV (208V - 38 kV)

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - Per customer specification IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - Per customer specification NEMA 1 wall-mounted construction
Operating Temperature - Per customer specification 0°C to 50°C
Storage Temperature - Per customer specification -20°C to +60°C
Low Voltage Standards - Per customer specification NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - Per customer specification NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • Cat XLM Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Energy Capacity Expansion (ECE) module Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • Temporary Connection Boxes Add
  • XQP550 EU Stage V Add