Compare Equipment Go Back

DG125 (Single-phase and 3 phase) (60 Hz)
Cat Customizable Switchgear and Controls
Cat XLM Switchgear

Generator Set Specifications

Frequency 60 Hz - -
Gas Standby Rating 125 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency and Non-Emergency Application - -
Voltage 208-600 - -
Speed 1800 rpm - -
Natural Gas Rating 125 ekW - -

Engine Specifications

Engine Model V8, 6.2L TCAC - -
Bore 4 in - -
Stroke 3.75 in - -
Displacement 378.3 in³ - -
Compression Ratio 9.8:1 - -
Aspiration TCAC - -
Fuel System Electronic - -

Generator Set Dimensions

Length 96 in - -
Width 51 in - -
Height 57 in - -
Dry Weight - Genset 3226 lb - -

Technical Summary

Configuration - Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation - All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application - LV and MV ( 208V - 38 kV) 50 / 60 Hz LV and MV ( 208V - 38 kV

Generator Protective Devices

ANSI Protective Devices - Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - Per customer specification 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86

Environmental Parameters

Certifications - Per customer specification IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure - Per customer specification NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature - Per customer specification 0 degrees to 50 degrees C
Storage Temperature - Per customer specification -20 degrees C to +60 degrees C
Low Voltage Standards - Per customer specification NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - Per customer specification NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Switchgear Add
  • EMCP 4.4 Master Control Panel Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • Temporary Connection Boxes Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add