Compare Equipment Go Back
DG100 (60 Hz) |
Cat XLM Switchgear |
|
|
Generator Set Specifications |
|||
---|---|---|---|
Frequency | 60 Hz | - | - |
Gas Standby Rating | 100 ekW | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application | - | - |
Speed | 1800 rpm | - | - |
Voltage | 208-600 | - | - |
Engine Specifications |
|||
Engine Model | V8, 6.2L TCAC | - | - |
Stroke | 3.75 in | - | - |
Displacement | 378.3 in³ | - | - |
Compression Ratio | 9.8:1 | - | - |
Aspiration | TCAC | - | - |
Bore | 4 in | - | - |
Fuel System | Electronic | - | - |
Generator Set Dimensions |
|||
Length | 96 in | - | - |
Width | 51 in | - | - |
Height | 57 in | - | - |
Dry Weight - Genset | 3007 lb | - | - |
Technical Summary |
|||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | - |
Modes of Operation | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | - |
Application | - | LV and MV ( 208V - 38 kV | - |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | - |
Utility Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | - |
Environmental Parameters |
|||
Certifications | - | IBS, CBC, UBC & OSHPD Certified | - |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R, Freestanding Construction | - |
Operating Temperature | - | 0 degrees to 50 degrees C | - |
Storage Temperature | - | -20 degrees C to +60 degrees C | - |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | - |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | - |
Add a Similar Product:
- Cat Customizable Switchgear and Controls Add
- Cat Switchgear Add
- EMCP 4.4 Master Control Panel Add
- Cat EGP Switchgear Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Engine Paralleling and Integration Control (EPIC) Add
- Energy Capacity Expansion (ECE) module Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- XQ425 Add