DG100 (60 Hz) |
Cat XLM Switchgear |
Cat Customizable Switchgear and Controls |
|
Generator Set Specifications |
|||
---|---|---|---|
Frequency | 60 Hz | - | - |
Gas Standby Rating | 100 ekW | - | - |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application | - | - |
Speed | 1800 rpm | - | - |
Voltage | 208-600 | - | - |
Engine Specifications |
|||
Engine Model | V8, 6.2L TCAC | - | - |
Stroke | 3.75 in | - | - |
Displacement | 378.3 in³ | - | - |
Compression Ratio | 9.8:1 | - | - |
Aspiration | TCAC | - | - |
Bore | 4 in | - | - |
Fuel System | Electronic | - | - |
Generator Set Dimensions |
|||
Length | 96 in | - | - |
Width | 51 in | - | - |
Height | 57 in | - | - |
Dry Weight - Genset | 3007 lb | - | - |
Technical Summary |
|||
Configuration | - | Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications | Application-specific switchgear with control logic designed to meet any customer's sequence of operations. Examples are 3+ Utilities, CHP applications, complex load shed schemes, etc |
Modes of Operation | - | Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power | All modes of paralleling generator sets to each other and to other sources (utility, alternative fuels, wind, etc) can be supported. Caterpillar generation and control experts can design and program the most complex power schemes to meet your critical pow |
Application | - | LV and MV ( 208V - 38 kV | LV and MV ( 208V - 38 kV) 50 / 60 Hz |
Generator Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 50, 51 | Per customer specification |
Utility Protective Devices |
|||
ANSI Protective Devices | - | 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 | Per customer specification |
Environmental Parameters |
|||
Certifications | - | IBS, CBC, UBC & OSHPD Certified | Per customer specification |
Control Panel Enclosure | - | NEMA 1 or NEMA 3R, Freestanding Construction | Per customer specification |
Operating Temperature | - | 0 degrees to 50 degrees C | Per customer specification |
Storage Temperature | - | -20 degrees C to +60 degrees C | Per customer specification |
Low Voltage Standards | - | NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 | Per customer specification |
Medium Voltage Standards | - | NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 | Per customer specification |
Add a Similar Product:
- Cat Switchgear Add
- EMCP 4.4 Master Control Panel Add
- Cat EGP Switchgear Add
- Engine Paralleling and Integration Control (EPIC) Add
- Cat® BDP1000 Bi-Directional Power Inverter Add
- Temporary Connection Boxes Add
- Energy Time Shift (ETS) Module Add
- Energy Capacity Expansion (ECE) module Add
- XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
- XQP550 EU Stage V Add