Compare Equipment Go Back

DG100 (60 Hz)
Cat XLM Switchgear
EMCP 4.4 Master Control Panel

Generator Set Specifications

Frequency 60 Hz - -
Gas Standby Rating 100 ekW - -
Emissions/Fuel Strategy U.S. EPA Certified for Stationary Emergency Application - -
Speed 1800 rpm - -
Voltage 208-600 - -

Engine Specifications

Engine Model V8, 6.2L TCAC - -
Stroke 3.75 in - -
Displacement 378.3 in³ - -
Compression Ratio 9.8:1 - -
Aspiration TCAC - -
Bore 4 in - -
Fuel System Electronic - -

Generator Set Dimensions

Length 96 in - -
Width 51 in - -
Height 57 in - -
Dry Weight - Genset 3007 lb - -

Technical Summary

Configuration - Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications Remote monitoring and control for up to 8 generator sets via high-speed network. Enables paralleling a group of EMCP 4.4 equipped generator sets to a single utility source.
Modes of Operation - Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power Emergency standby, island, utility paralleling
Application - LV and MV ( 208V - 38 kV LV and MV (208V - 38 kV)

Generator Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Utility Protective Devices

ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86 15/25. 27/59, 81 O/U, 32,47 (Industrial Grade)

Environmental Parameters

Certifications - IBS, CBC, UBC & OSHPD Certified IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure - NEMA 1 or NEMA 3R, Freestanding Construction NEMA 1 wall-mounted construction
Operating Temperature - 0 degrees to 50 degrees C 0°C to 50°C
Storage Temperature - -20 degrees C to +60 degrees C -20°C to +60°C
Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70 NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110 NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Add a Similar Product:
  • Cat Customizable Switchgear and Controls Add
  • Cat Switchgear Add
  • Cat EGP Switchgear Add
  • Engine Paralleling and Integration Control (EPIC) Add
  • Cat® BDP1000 Bi-Directional Power Inverter Add
  • Temporary Connection Boxes Add
  • Energy Time Shift (ETS) Module Add
  • Energy Capacity Expansion (ECE) module Add
  • XQ570 Tier 4 Final – 455 ekW (568 kVA) Add
  • XQP550 EU Stage V Add