CALL US: 800-937-2326  

Cat EGP Switchgear


Caterpillar offers standard Switchgear products, which can support a wide variety of applications, or provide a custom designed system to meet your specific project needs. The Emergency Generator paralleling (EGP) product supports paralleling on an isolated generator bus and is commonly used in prime power or emergency standby systems. Caterpillar Standard Switchgear products provide a solution able to combine all elements of monitoring and control for Caterpillar generator sets in a single-source package. Caterpillar also designs and manufacturers custom switchgear to meet specific customer requirements and functionality.

Technical Summary
  • Configuration - Traditional customizable PLC based floor standing switchgear capable of controlling and monitoring multiple utilities, generators, and loads
  • Modes of Operation - Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
  • Application - LV and MV (208V - 38 kV)
  • Generator Protective Devices
  • ANSI Protective Devices - 15/25, 27/59, 81 O/U, 32, 40, 50, 51
  • Environmental Parameters
  • Certifications - IBC, CBC, UBC & OSHPD Certified
  • Control Panel Enclosure - NEMA 1 or NEMA 3R Freestanding Construction
  • Operating Temperature - 0°C to 50°C
  • Storage Temperature - -20°C to +60°C
  • Low Voltage Standards - NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
  • Medium Voltage Standards - NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
  • Standard Equipment
  • EGP Switchgear
  • Optional Equipment
  • Data Table Interface
  • Supplemental Hardware Synchronization check relay (ANSI 25 Device)
  • Remote Power Monitoring System

    You can only compare up to two models. Please remove one of your current selections before making another.